首页> 外文会议>IEEE electrical insulation conference >Limitations to the determination of water content in transformers solid insulation from measurement of water in oil
【24h】

Limitations to the determination of water content in transformers solid insulation from measurement of water in oil

机译:局限性测定变压器固体绝缘中的水中水中的水

获取原文

摘要

Determination of the water content in the winding insulation of aging transformers is an essential part of their condition assessment. Since this insulation cannot be accessed directly on a transformer in service, the moisture content has to be inferred from other available measurements. One method frequently applied is to measure the water content in the insulating oil and use a set of physical relationships to determine the water content in the winding insulation. This method is now being deployed on a larger scale as the availability of on-line monitoring devices grows. This paper reviews the limitations intrinsic to this method and assesses the overall accuracy that can be expected for a transformer in service under varying operating conditions. It is concluded that for most cases of interest the accuracy is about ±20% but, for very dry transformers, the uncertainty may rise above ±40%.
机译:衰老变压器绕组绝缘中的含水量的测定是其条件评估的重要组成部分。由于该绝缘不能直接在服务中的变压器上访问,因此必须从其他可用测量中推断出水分含量。经常应用的一种方法是测量绝缘油中的水含量,并使用一组物理关系来确定卷绕绝缘中的水含量。随着在线监测设备的可用性增长,此方法现在正在进行更大的比例。本文综述了该方法的内在内部的限制,并评估了在不同操作条件下提供的变压器可以预期的整体精度。得出结论是,对于大多数感兴趣的情况来说,精度约为±20%,但对于非常干燥的变压器,不确定性可能上升到±40%以上。

著录项