Conventional Restricted earth fault protection provides protection about 80 to 90% of generator stator winding against earth fault when neutral of generator is earthed through a resistance. In this paper, superconducting fault current limiter an innovative device is used along with restricted earth fault protection to provide 100% stator earth fault protection. A specific generator is considered which is provided with restricted earth fault protection to protect 90% of its winding against earth fault. Then a resistive SFCL is applied in the protective scheme replacing the neutral earthed resistance to a lower value than the previous one. It is found that excellent operational characteristics of SFCL facilitate the restricted earth fault relay to operate from very beginning to the end of the generator winding and provide 100% stator earth fault protection.
机译:当发电机的中性点通过电阻接地时,常规的受限接地故障保护可为发电机定子绕组的80%至90%的接地故障提供保护。本文将一种创新的超导故障限流器与受限制的接地故障保护一起使用,以提供100%的定子接地故障保护。考虑一种特定的发电机,该发电机具有受限制的接地故障保护,以保护其90%的绕组免受接地故障的影响。然后在保护方案中应用电阻式SFCL,将中性点接地电阻替换为比前一个更低的值。可以发现,SFCL的出色工作特性使受限制的接地故障继电器从发电机绕组的最开始到结束都可以工作,并提供了100%的定子接地故障保护。