The disproportion in natural resource and power load results in lots of 500kV transmission lines in southern China. These transmission lines are seriously influenced by lightning because of the complex terrain and frequent lightning activities in southern China. In this paper, lightning performance of six 500kV transmission lines in southern China is analyzed with the help of Lightning Protection Analyzing System for Transmission Line (LPTL). The simulation is based on the method recommended by IEEE standard, considering the geographical environment and structure of each tower. The results show the existing difference in lightning performance of each tower. Then comparative analysis is made between the simulation results and operation experience on flashover rate of entire line. It indicates that the IEEE method considering practical situation is available to the lightning performance assessment of 500KV transmission lines in southern China.
机译:自然资源和电力负荷的不均衡导致了华南地区大量的500kV输电线路。由于中国南部地形复杂,雷电活动频繁,这些传输线受到雷电的严重影响。本文借助输电线路防雷分析系统(LPTL),对华南地区六条500kV输电线路的防雷性能进行了分析。模拟基于IEEE标准推荐的方法,并考虑了每个塔的地理环境和结构。结果表明,每座塔的雷电性能存在差异。然后对仿真结果和运行经验对整条线的闪络率进行了比较分析。这表明考虑到实际情况的IEEE方法可用于中国南方500KV输电线路的雷电性能评估。