首页> 外文会议>IEEE International Conference on Power Electronics, Drives and Energy Systems >Line harmonic current effects study of a 33 kW, 3-Phase 60 Hz, 12-pulse transformer using 'Double-2D' FEA model
【24h】

Line harmonic current effects study of a 33 kW, 3-Phase 60 Hz, 12-pulse transformer using 'Double-2D' FEA model

机译:使用“双2D”FEA模型,线谐波电流效果研究33千瓦,3阶段60Hz,12脉冲变压器

获取原文

摘要

This paper presents an analysis of the skin and proximity effects produced by line frequency harmonic currents in a 33 kW 12-pulse rectifier transformer using its "Double-2D" FEA model. The model is first validated with experimental data obtained from a series of standard impedance voltage tests with a proof-of-concept transformer prototype. Good agreement is observed between model results and experimental data. The model is then used to study the 12-pulse harmonic current conditions and represent the associated winding losses as equivalent resistances. It is seen that harmonic current losses account for as much as 8-11% of the secondary winding and 4-6% of the total winding power loss, indicating their significance in this application.
机译:本文采用了使用其“双2D”FEA模型在33 kW 12脉冲整流器变压器中通过线频谐波电流产生的皮肤和接近效果的分析。 该模型首先用来自一系列标准阻抗电压测试获得的实验数据,该试验数据具有概念验证变压器原型。 在模型结果和实验数据之间观察到良好的一致性。 然后使用该模型来研究12脉冲谐波电流条件,并表示相关的绕组损耗作为等效电阻。 可以看出,谐波电流损失占二次绕组的8-11%,占总绕组功率损失的4-6%,表明其在本申请中的重要性。