Electronic voltage transformer (EVT) and electronic current transformer (ECT) are important equipments in smart grid. In order to meet the requirements of power reliability in the grid, the annual failure rate of EVT and ECT should be less than 0.2% during normal operation. Power transformer is the electrical device, its annual failure rate is only 0.01%, and the comprehensive reliability of secondary relay protection devices can be improved to more than 99.8% by redundancy design. EVT and ECT's reliability can be hardly improved to 99.8% due to the limit of failure relevance, unless designed and manufactured according to aerospace standards. EVT and ECT's utilization is limited in the digital substation considering of reliability and economy. In the digital substation, Non-traditional transformer is an economical and rational design, because the reliability of 99.8% can be guaranteed by sending analog small-signals from non-traditional transformers to the relay unit. Non-traditional transformer's analog output is sent to the merged cell of transformer, and a digital signal is converted into the data bus serving for substation monitoring and control systems, so the reliability can reach 99%. Thus non-traditional transformer's analog output and merged cell's output can respectively meet the reliability requirements of relay protection and monitoring system's informatization in the digital substation.
机译:电子电压变压器(EVT)和电子电流互感器(ECT)是智能电网的重要设备。为了满足网格中功率可靠性的要求,在正常运行期间,EVT和ECT的年失效率应小于0.2%。电力变压器是电气设备,其年故障率仅为0.01%,二次继电器保护装置的综合可靠性可以通过冗余设计提高到99.8%以上。除非根据航空航天标准设计和制造,否则EVT和ECT的可靠性可能几乎没有提高到99.8%。考虑到可靠性和经济的数字变电站,EVT和ECT的利用率有限。在数字变电站中,非传统变压器是一种经济型和合理的设计,因为通过将非传统变压器的模拟小信号从非传统变压器发送到继电器单元,可以保证99.8%的可靠性。非传统变压器的模拟输出被发送到变压器的合并单元格,数字信号被转换为用于变电站监测和控制系统的数据总线,因此可靠性可以达到99%。因此,非传统变压器的模拟输出和合并的单元格的输出可以分别符合中继保护和监控系统信息化的可靠性要求在数字变电站中。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号