Sizing and selection of grounding transformers-decision criteria

机译:接地变压器的尺寸和选择-判定标准

获取原文

摘要

Within a period of two years, the Electricity Company of Ghana (ECG) lost a total of six grounding transformers in a particular substation. The situation created a lot of instability and resulted in huge productivity losses to both the company and its customers. The failures were believed to be related to wrong selection of grounding transformer rating. However, using the concept of capacitive charging current of a system, it was found that the short time rating of the grounding transformers were rightly selected. Analysis of the phenomenon strongly linked the damages to protection deficiency. This paper discusses analysis of the problem and proposes decision criteria for selecting a grounding transformer.
机译:在两年的时间内,加纳电力公司(ECG)在一个特定的变电站中总共损失了6台接地变压器。这种情况造成了很大的不稳定,并给公司及其客户造成了巨大的生产力损失。人们认为这些故障与接地变压器额定值的选择错误有关。但是,使用系统的电容充电电流的概念,发现正确选择了接地变压器的短时额定值。对这一现象的分析将损害与保护不足紧密联系在一起。本文讨论了问题的分析,并提出了选择接地变压器的决策标准。