首页> 外文会议>ASME international heat transfer conference;IHTC14 >VIABILITY STUDY OF RETRIEVING THE EVAPORATED WATER IN A MECHANICAL DRAFT CROSS FLOW COOLING TOWER
【24h】

VIABILITY STUDY OF RETRIEVING THE EVAPORATED WATER IN A MECHANICAL DRAFT CROSS FLOW COOLING TOWER

机译:机械贯流冷却塔回收蒸发水的可行性研究。

获取原文

摘要

Cooling towers use evaporative heat transfer to reduce process water temperature. In mostly cases, the amount of water lost to evaporation is irrelevant, but in the present case of study, the amount of makeup water due to evaporation, is around 700 m3/h. That alone is a considerable amount of fresh water that needs to be removed from the local rivers and is currently having a negative impact in the fresh water availability for consumption. This study explores viable solutions to recover some of the evaporated water, but not compromising the effectiveness of the cooling tower.The plant is located in the southeast region of Brazil where temperature and humidity vary considerably along the year. The present study focuses on retrieving the evaporated water through condensation and capturing fog without compromising the cooling tower performance. Data from the actual cooling tower was used in the thermodynamic analysis. Computational fluid dynamics (CFD) was used to simulate the mixing of air leaving the cooling tower with outdoor air. An experimental setup is also being developed to reproduce the condensation process.
机译:冷却塔使用蒸发传热来降低过程水的温度。在大多数情况下,蒸发损失的水量无关紧要,但在本研究案例中,由于蒸发而产生的补充水量约为700立方米/小时。仅此一项就需要从当地河流中去除大量淡水,目前对淡水的消费量产生负面影响。这项研究探索了可行的解决方案,以回收一些蒸发的水,但不影响冷却塔的效率。 该工厂位于巴西的东南部地区,全年温度和湿度变化很大。本研究的重点是通过冷凝水回收蒸发水并捕获雾气而不损害冷却塔的性能。来自实际冷却塔的数据用于热力学分析。计算流体动力学(CFD)用于模拟离开冷却塔的空气与室外空气的混合。还正在开发实验装置以重现冷凝过程。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号