Effects of under-voltage trip devices in distribution network and end users on power systems and suggestions

机译:配电网和最终用户的低压脱扣装置对电力系统的影响和建议

获取原文

摘要

Currently, under-voltage trip devices are widely installed in circuit breakers of low-voltage distribution networks and end users' sides. These protection devices can prevent equipments from damage when voltage sag or power supply interruption occurs. Although relay protection devices can act correctly and clear the fault as soon as possible when a ground or inter phase fault occurs in the nearby high-voltage transmission network, instantaneous action of under-voltage trip devices may lead to widespread loss of load, fluctuation of frequency, even worse, cascading failure and collapse of the power system. The widespread load loss accidents arising from under-voltage trip devices happened in recent years are summarized in this paper. Two typical load loss accidents happened in Beijiao substation are introduced. The effects of under-voltage trip devices on power system are discussed base on EMS accident recall, PMU, fault recorder and other tools. Finally, suggestions on management of under-voltage trip devices and accident precautions are proposed.
机译:当前,低压脱扣装置被广泛地安装在低压配电网的断路器和最终用户侧。这些保护装置可以防止电压骤降或电源中断时损坏设备。尽管在附近的高压输电网络中发生接地或相间故障时,继电保护装置可以正确动作并尽快清除故障,但欠压跳闸装置的瞬时动作可能会导致负载的广泛损失,电网波动。频率,甚至更糟糕的是,连锁故障和电力系统崩溃。本文总结了近年来发生的因欠电压脱扣装置而引起的广泛的负载损失事故。介绍了北郊变电站发生的两起典型的负荷损失事故。基于EMS事故召回,PMU,故障记录仪和其他工具,讨论了欠压脱扣装置对电力系统的影响。最后,提出了欠电压跳闸装置的管理和事故预防措施的建议。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号