首页> 外文会议>2010 4th International Conference on Bioinformatics and Biomedical Engineering >Study of Air Conditioning System with Purifier in a Gymnasium
【24h】

Study of Air Conditioning System with Purifier in a Gymnasium

机译:体育馆净化器空调系统的研究

获取原文

摘要

The purpose of this study was to find the effective control of bacterial and fungal bioaerosol in a gymnasium. Airborne bacteria and fungi were collected using the 6-stage Andersen impactor inside and outside of gymnasium. Purification method is to install HEPA filters at air inlet. It was found that the total concentrations of outdoor airborne bacteria and fungi were 895CFU/m3 and 1505CFU/m3 around the gymnasium in Beijing in summer. The total levels of bacterial and fungal aerosol indoors were averaged to 831CFU/m3 in the case of no one, and in the case of some one is 1860CFU/m3. Before and after the setting of the purifier the total levels of bacterial and fungal aerosol indoors were 1216CFU/m3 and 1860CFU/m3. Outside of the gymnasium the bacterial aerosols and the fungal aerosols showed the highest collection rates at F-1, F-3 stage and F-4, F-5 stage separately, while inside of the gymnasium at F-4, F-5 stage contemporary.
机译:这项研究的目的是在体育馆中找到对细菌和真菌生物气溶胶的有效控制。在体育馆内外使用6级安徒生撞击器收集空气传播的细菌和真菌。净化方法是在进气口安装HEPA过滤器。结果发现,夏季北京体育馆周围室外空气中细菌和真菌的总浓度为895CFU / m3和1505CFU / m3。在没有人的情况下,室内细菌和真菌气溶胶的总水平平均为831CFU / m3,在有人的情况下,平均值为1860CFU / m3。在设置净化器之前和之后,室内细菌和真菌气溶胶的总含量为1216CFU / m3和1860CFU / m3。在体育馆外部,细菌气溶胶和真菌气溶胶分别在F-1,F-3和F-4,F-5阶段表现出最高的采集率,而在体育馆内部则在F-4,F-5阶段当代的。