首页> 外文会议>2010 China International Conference on Electricity Distribution >Impact of abnormality of bus coupler TWJ on dead-zone protection of bus coupler
【24h】

Impact of abnormality of bus coupler TWJ on dead-zone protection of bus coupler

机译:TWJ总线耦合器异常对总线耦合器死区保护的影响

获取原文

摘要

In the testing of bus protection,it is found that the dead-zone protection of coupler will fail to operate when bus coupler TWJ cannot act correctly for the reason of contact adherence or jam. By analyzing of the theory and logic diagram of dead-zone protection of coupler, it is presented that the cause of incorrect action of dead-zone protection of coupler is that the bus coupler current is not excluded from the differential bus protection correctly. A new method is proposed to avoid this defect by the leading-in of bus coupler HWJ, then the improved logic diagram is given and analyzed. The analysis results show that the practical engineering value of this method is great because the rejecting operation of dead-zone protection can be avoided and the operation time of protection can be shortened by using it.
机译:在母线保护的测试中,发现当母线耦合器TWJ由于接触粘连或卡住而无法正确动作时,耦合器的死区保护将无法工作。通过对耦合器死区保护理论和逻辑图的分析,指出耦合器死区保护动作不正确的原因是母线耦合器电流没有正确地从差动母线保护中排除。提出了一种通过引入总线耦合器HWJ来避免这种缺陷的新方法,然后给出并分析了改进的逻辑图。分析结果表明,该方法可避免死区保护的拒收操作,缩短了保护的工作时间,具有较大的工程实用价值。