Influence of air pressure on positive DC corona inception voltage of stranded conductors in the corona cage

机译:气压对电晕笼中绞合导体的正直流电晕起始电压的影响

获取原文

摘要

The transmission lines pass by the high altitude region with low air pressure, which brings many special problems to the design and operation of the transmission lines. The corona cage is widely used to study the corona performance of conductors for its good economy and maneuverability. A computation model is adopted for evaluating the corona inception voltages of conductors in the corona cage, which is established according to the gas discharge theory. The charge simulation method is introduced to the computation model to calculate the electric field intensity. Then the positive corona inception voltage are calculated according to the positive corona criterion. The influence of air pressure on the corona inception voltage of conductors is analysed systematically. Corona inception voltage decreases as air pressure is lowered. The corona inception voltage may decrease by 9% per 0.01MPa bases on the standard atmospheric pressure, which is mainly due to the enlargement of ionization zone as a result of the increase of effective ionization coefficient.
机译:输电线路通过高气压低气压的高海拔地区,给输电线路的设计和运行带来许多特殊问题。电晕笼由于其良好的经济性和可操作性而被广泛用于研究导体的电晕性能。采用计算模型对电晕笼中导体的电晕起始电压进行评估,该模型是根据气体放电理论建立的。将电荷模拟方法引入计算模型以计算电场强度。然后根据正电晕准则计算正电晕起始电压。系统分析了气压对导体电晕起始电压的影响。随着气压的降低,电晕起始电压降低。基于标准大气压,电晕起始电压每0.01MPa可能会降低9%,这主要是由于有效电离系数的增加导致电离区的扩大。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号