首页> 外文会议>2010 International Conference on Power System Technology >Adjusting for the unblance of capacitor banks with H-bridge connection of power filter on UHVDC converter station
【24h】

Adjusting for the unblance of capacitor banks with H-bridge connection of power filter on UHVDC converter station

机译:通过HVDC换流站中的电源滤波器的H桥连接来调整电容器组的不平衡

获取原文

摘要

A method for adjusting the unbalance of the capacitor banks with H-bridge connection of the power filter on UHVDC converter station in this paper. Firstly, the concept of unbalance degree is proposed, and the expression of the unbalance degree is deduced, then the new method for adjusting the unbalance of the capacitor bank with H-bridge connection is put forward. The detection method is adopted to detect and adjust the unbalance of the capacitor with H-bridge connection. The test result shows that the proposed method could improve the work efficiency greatly, and the method is suitable for field commissioning test in UHVDC converter station.
机译:本文提出了一种通过特高压直流换流站的电源滤波器的H桥连接来调节电容器组不平衡的方法。首先提出了不平衡度的概念,推导了不平衡度的表达式,然后提出了一种通过H桥连接来调节电容器组不平衡度的新方法。采用这种检测方法,可以检测和调整H桥连接的电容器的不平衡度。测试结果表明,该方法可以大大提高工作效率,适用于特高压直流换流站的现场调试测试。