首页> 外文会议>2010 International Conference on High Voltage Engineering and Application >Research on the dielectric properties and breakdown voltage of transformer oil-paper insulation after accelerating thermal ageing
【24h】

Research on the dielectric properties and breakdown voltage of transformer oil-paper insulation after accelerating thermal ageing

机译:加速热老化后变压器油纸绝缘的介电性能和击穿电压的研究

获取原文

摘要

In this paper, a set of accelerate thermal ageing experiments on oil immersed insulation paper were performed under 110❐ and lasted for more than 100 days. The degree of polymerization (DP), the frequency domain spectroscopy (FDS) and water concentration in insulating oil and paper, as well as the AC breakdown voltage of insulation paper were tested and analyzed. The results indicate that the dielectric properties can be used as indicators for the degradation evaluation of insulation paper. And the breakdown voltage of paper showed very little difference after accelerating thermal ageing, the electrical strength of oil-paper insulation system depends mainly on the performance of insulating oil.
机译:本文对油浸绝缘纸进行了一组加速热老化试验,试验温度为110❐,历时100天以上。对绝缘油和绝缘纸中的聚合度(DP),频域光谱(FDS)和水浓度以及绝缘纸的AC击穿电压进行了测试和分析。结果表明,介电性能可以作为绝缘纸降解评估的指标。加速热老化后,纸的击穿电压差异很小,油纸绝缘系统的电气强度主要取决于绝缘油的性能。