首页> 外文会议>Power and Energy Engineering Conference (APPEEC), 2010 >Time Domain Fault Location Method Based on UHV Transmission Line Parameter Identification Using Two Terminal Data
【24h】

Time Domain Fault Location Method Based on UHV Transmission Line Parameter Identification Using Two Terminal Data

机译:基于两个终端数据的特高压输电线路参数辨识的时域故障定位方法

获取原文

摘要

A time domain fault location method by identifying line parameters using two-terminal data is proposed. The method does not need accurate values of parameters to be given. In the condition that the fault point voltage values calculated from data at both ends are identical, the line parameters can be identified, and, meanwhile, the fault distance can be determined, eliminating the errors of traditional fault location algorithms caused by the inaccurate given parameters. As the percentage fault distance is used, the influence of seasonal and sagging-induced change in line length is well overcome, thus enabling accurate and quick search for fault point through measurement of actual ground distance between poles and towers. Simulation results show the proposed method is feasible and has high accuracy of fault location and line parameter identification.
机译:提出了一种通过使用双终端数据识别线参数的时域故障定位方法。该方法不需要提供准确的参数值。在从两端的数据计算的故障点电压值相同的情况下,可以识别线参数,同时可以确定故障距离,从而消除了由不准确的参数引起的传统故障定位算法的错误。随着使用百分比的故障距离,季节性和下垂引起的线条长度变化的影响很好地克服,从而通过测量杆和塔之间的实际接地距离来实现准确和快速地搜索故障点。仿真结果表明,所提出的方法是可行的,具有高精度的故障位置和线参数识别。