首页> 外文会议>Power and Energy Engineering Conference (APPEEC), 2010 >Voltage Supporting Strength Evaluation Of The HVDC Receiving Grid In Synchronous And Asynchronous Interconnecting Power System
【24h】

Voltage Supporting Strength Evaluation Of The HVDC Receiving Grid In Synchronous And Asynchronous Interconnecting Power System

机译:同步,异步互联电力系统高压直流输电电网的电压支持强度评估

获取原文

摘要

This paper simulates the voltage sags caused by HVDC failures in both the asynchronous interconnecting and the AC/DC parallel power systems and studies their relationships with the short circuit ratio (SCR) series indices. It's found that in the asynchronously interconnected power system the SCR indices can quantitatively indicate the voltage supporting ability of the receiving-end AC system under HVDC failures. However in the AC/DC parallel system the SCR indices are ineffective. An improved SCR index is then proposed to solve the problem. Simulations prove its feasibility in the AC/DC parallel power systems.
机译:本文模拟了异步互连和AC / DC并联电源系统中由HVDC故障引起的电压骤降,并研究了它们与短路比(SCR)串联指标的关系。发现在异步互连的电力系统中,SCR指数可以定量指示HVDC故障下接收端交流系统的电压支持能力。但是,在AC / DC并联系统中,SCR指数无效。然后,提出了一种改进的SCR指数来解决该问题。仿真证明了其在交流/直流并联电源系统中的可行性。

著录项