Partial discharge (PD) can be one of the most influential phenomena in the aging of electrical insulation systems. In order to ensure reliability in the operation of such equipment, the detection and interpretation of PD measurements is required to monitor the condition of insulation. In this paper, physical model of typical defects in gas-insulated substation (GIS) are established, and studied for PD using Pulse current method, which are based on the characteristics of defects and PD checker instrument. The results show that the phase-resolved PD (PRPD) patterns, the time domain waveforms, average amplitude and central phase changing of PD signals have very similar distribution characteristics and those of different defect have different ones. So it would be very convenient for the recognition of PD types and a deeper study of the mechanism of PD.
机译:局部放电(PD)可能是电气绝缘系统老化中最有影响力的现象之一。为了确保此类设备运行的可靠性,需要对PD测量值进行检测和解释,以监控绝缘状况。本文建立了气体绝缘变电站(GIS)典型缺陷的物理模型,并根据缺陷特征和局部放电检测仪,采用脉冲电流法对局部放电进行了研究。结果表明,PD信号的相位分辨PD(PRPD)模式,时域波形,平均幅度和中心相位变化具有非常相似的分布特征,而具有不同缺陷的PD信号具有不同的分布特征。因此,对于PD类型的识别和PD机理的深入研究将非常方便。