The control of a ClO2 generator has relied mainly on manual analyses of generator liquor and the use of temperature as an indication of acid concentrations. Due to the highly corrosive and hazardous environment of an R8 ClO2 generator, manual sampling poses further risks to testers and operators in the vicinity. At Catalyst Paper's Crofton mill, a project was carried out to install the FT-NIR analyser for automated at-line measurements of acid and chlorate strength. The measurements were then utilized for closed loop control of the R8 generator and has allowed for reduction in manual testing, improved efficiency. Recently, the measurements of sesquisulfate solids content and residual ClO2 has been added to the FT-NIR and these results are used for forecasting potential generator problems. The paper will discuss the results obtained from the FT-NIR ClO2 generator analyser for acid and chlorate strength as well as the sesquisulphate solids and residual ClO2 concentration dissolved in the liquor.
机译:ClO 2发生器的控制主要依靠发生器液的手动分析和使用温度作为酸浓度的指示。由于R8 ClO2发生器具有高度腐蚀性和危险性,因此手动采样会对附近的测试人员和操作人员带来进一步的风险。在Catalyst Paper的Crofton工厂,进行了一个项目,安装FT-NIR分析仪,用于在线自动测量酸和氯酸盐强度。然后将这些测量值用于R8发生器的闭环控制,并减少了手动测试,提高了效率。最近,对倍半硫酸盐固体含量和残留ClO2的测量已添加到FT-NIR中,这些结果用于预测潜在的发电机问题。本文将讨论从FT-NIR ClO2发生器分析仪获得的有关酸和氯酸盐强度以及倍半硫酸盐固体和溶解在白酒中的残留ClO2浓度的结果。