With the continuous development of urban construction in Shanghai Shinan area, the 10 kV power grids have developed rapidly. More and more cables have been used, which resulted in the growing of capacitive current. Based on the actual grid situations of Shinan area and the measured capacitive current of nine substations, a basic criterion has been concluded for adjusting the neutral point grounding mode from grounding through arc suppression coil to grounding through low resistance after technically analyzing. The criterion is instructive for selecting the neutral point grounding mode of newly built substations and the rebuilt ones. In the last three years, two substations have been rebuilt to change the neutral point grounding mode based on the criterion. The subsequent actual operation of the two substations has proved the feasibility of the criterion.
机译:随着上海市南地区城市建设的不断发展,10 kV电网发展迅速。越来越多的电缆被使用,导致电容电流的增加。根据石南地区的实际电网情况和九个变电站测得的电容电流,经过技术分析,得出了将中性点接地方式从消弧线圈接地改为低阻接地的基本准则。该标准对于选择新建和改建变电站的中性点接地方式具有指导意义。在过去的三年中,已经根据此标准对两个变电站进行了改造,以改变中性点接地方式。随后两个变电站的实际运行证明了该标准的可行性。