首页> 外文会议>China International Conference on Electricity Distribution >Adaptability analysis of differential protection for UHV half-wavelength AC transmission line
【24h】

Adaptability analysis of differential protection for UHV half-wavelength AC transmission line

机译:UHV半波长AC输电线路差动保护的适应性分析

获取原文

摘要

Relay protection is one of problems troubling the development of half-wavelength AC transmission technology. This paper modeled the half-wavelength line with the distributed parameter, researched the fault characteristics and the adaptability of phase-splitting steady current differential protection theoretically and through plenty of simulation work, and analyzed its influencing factors from three respects. The result indicates that conventional steady differential protection algorithm is not very suitable for half-wavelength transmission, the sensitivity of middle range is the biggest problem. Then adaptability of zero sequence current differential protection and differential protection based on deviation of power frequency component are researched, the simulation results indicate they have better sensitivity. The research result shows the differential protection can be set as backup protection, and need to coordinate with the quick protection which protect the range close to two ends.
机译:继电保护是困扰半波长交流传输技术的问题之一。本文用分布式参数建模了半波长线,研究了故障特性和大量模拟工作的相相稳定电流差动保护的故障特性和适应性,并分析了三个方面的影响因素。结果表明,传统的稳态差分保护算法不是非常适合半波长传输,中间范围的灵敏度是最大的问题。然后,研究了零序电流差分保护和基于功率分量偏差的差分保护的适应性,模拟结果表明它们具有更好的灵敏度。研究结果表明,可以将差分保护设置为备份保护,并且需要与快速保护坐标,保护靠近两端的范围。