首页> 外文会议>China International Conference on Electricity Distribution >Comparison and analysis of protection latency time between intelligent and traditional substations
【24h】

Comparison and analysis of protection latency time between intelligent and traditional substations

机译:智能与传统变电站保护潜伏期的比较与分析

获取原文

摘要

In this paper, the protection latency time between traditional and intelligent substations are compared and analyzed. In traditional substation, the analog information such as current and voltage are tranmitted to the protection and control devices via electric cable, while in intelligent substation the introduction of digital protection devices and intelligent substation prolong the protection time, which brings safe threaten to the cutoff of power system fault. The compositions of operation latency time are compared in each link and two major different time latency links are analyzed in details, and the mechanism of time latency is investigated and the effective meausures to reduce the protection latency time are proposed. Finally, the experiment of protection time comparison between two is carried out and the results prove the validity of theoretical analysis.
机译:在本文中,比较和分析了传统和智能变电站之间的保护潜伏期。在传统的变电站中,电流和电压等模拟信息通过电缆迁移到保护和控制装置,而在智能变电站中,数字保护装置引入和智能变电站延长了保护时间,这使安全威胁到了截止的截止电源系统故障。在每个链路中比较操作延迟时间的组合物,并详细分析两个主要的不同时间延迟链路,并研究了时间延​​迟的机制,提出了减少保护潜伏时间的有效速度。最后,进行了两者之间的保护时间比较的实验,结果证明了理论分析的有效性。