首页> 外文会议>First International Conference on Wireless Internet, 2005. >Analysis of harmonic for 12-pulse converter under unbalancedvoltage operation due to lightning related voltage sags and shortinterruption
【24h】

Analysis of harmonic for 12-pulse converter under unbalancedvoltage operation due to lightning related voltage sags and shortinterruption

机译:不平衡条件下12脉冲变流器谐波分析由于雷电引起的电压骤降和短路而导致电压工作打断

获取原文

摘要

This paper presents a summary of power quality related concernsassociated with the applications of 12-pulse converter with DC motordrives in industrial plants. These concerns include power systemharmonics and harmonic distortion under unbalance voltage conditionduring voltage sags occurrence. The definition proposed focuses onsystem faults due to lightning. The voltage unbalance causes largeunbalance source currents resulting in excessive input current and highdistortion. The percentage of total harmonic distortion of input current(THDi) increased approximately 47% at 6 per unit of normalpeak current. The measurement and analysis of such events has beenperformed. Finally, the new phase-angle jump concept based on measuredtechniques is introduced
机译:本文提出了电能质量相关问题的摘要 与DC电机的12脉冲转换器的应用相关 在工业厂房驾驶。这些问题包括电力系统 不平衡电压条件下的谐波和谐波失真 在电压下垂期间发生。提出的定义重点介绍 闪电引起的系统故障。电压不平衡导致大 不平衡源电流导致输入电流过高和高 失真。输入电流的总谐波失真的百分比 ( i )每单位正常的6个增加约47% 峰值电流。对此类事件的测量和分析已经存在 表演。最后,基于测量的新相位角跳跃概念 介绍了技术