Generator circuit breakers must be able to carry operating currents of several 10 kA and short time currents of several 100 kA. It is shown how a generator circuit breaker to be developed can be optimized by calculation using the thermal network method and finite element models for high operating currents. The essential parameters are found out which mainly determine the temperatures of the conductor path and the contact systems. The parameters, which are needed for the calculation of the thermal network models and the optimization of the circuit breakers, were determined experimentally or by calculation (FEM).
机译:发电机断路器必须能够承受10 kA的工作电流和100 kA的短时间电流。它显示了如何通过使用热网络方法和有限元模型对高工作电流进行计算来优化要开发的发电机断路器。找出基本参数,这些参数主要决定导体路径和接触系统的温度。计算热网络模型和优化断路器所需的参数是通过实验或通过计算(FEM)确定的。