首页> 外文会议>Industrial and Commercial Power Systems Technical Conference, 1998 IEEE >Power quality monitoring enhances preventive maintenance program: detecting a substation transformer tap changer problem
【24h】

Power quality monitoring enhances preventive maintenance program: detecting a substation transformer tap changer problem

机译:电能质量监控增强了预防性维护程序:检测变电站变压器的分接开关问题

获取原文

摘要

This article discusses a power quality monitoring program underway between a semiconductor manufacturing facility and its serving utility, A description of the sophisticated monitoring program installed and maintained by the utility and a portion of the power quality monitoring installed within the manufacturing site distribution system is included. An incident, where monitoring pinpointed a utility substation transformer load tap changer problem, is presented in depth. The subsequent investigation and actions that took place to repair the tap changer without impacting the manufacturing facility are discussed. A fault in the tap changer compartment could have resulted if the tap changer problem had gone undetected. Steps taken to correct the tap changer problem averted a possible fault and subsequent transformer differential relay action.
机译:本文讨论了半导体制造厂及其服务公用事业公司之间正在进行的电能质量监控程序,包括对公用事业公司安装和维护的复杂监控程序以及安装在制造场所分配系统中的一部分电能质量监控器的描述。深入介绍了一个事件,在该事件中,监视确定了公用变电站变压器的有载分接开关问题。讨论了在不影响生产设备的情况下修理分接开关的后续调查和采取的措施。如果未发现分接开关问题,则可能导致分接开关仓发生故障。纠正分接开关问题的步骤避免了可能的故障以及随后的变压器差动继电器动作。