Analysis on effect of neutral grounding via high-resistance to arc grounding overvoltage

机译:高阻中性点接地对电弧接地过电压的影响分析

获取原文

摘要

This paper analyzes and compares the advantages and shortcomings of every kind of method on neutral grounding, presents the view of neutrla grounding via high-resistance in 3.3kV power supply. Considering the specialties that line-to-ground capacitance is very small at coalface electric network, the value of neutral grounding resistor may be increased properly, and gives out the formula on selecting value of resistor in details. Experimental results that are gotten in modeling 3.3kV electric network in lab are given out also.
机译:本文对中性点接地各种方法的优缺点进行了分析比较,提出了在3.3kV电源中通过高阻接地的方法。考虑到采煤面电网线地电容很小的特点,可以适当增加中性点接地电阻的值,并详细给出选择电阻值的公式。给出了在实验室对3.3kV电网进行建模的实验结果。