首页> 外文会议>The 2nd International Conference on Satellite Communications, 1996. Proceedings of ICSC '96, 1996 >Numerical algorithm for fault distance calculation and blocking unsuccessful reclosing onto permanent faults
【24h】

Numerical algorithm for fault distance calculation and blocking unsuccessful reclosing onto permanent faults

机译:故障距离计算和阻止不成功重合闸到永久故障的数值算法

获取原文

摘要

This paper presents a new numerical spectral domain algorithm devoted to blocking unsuccessful automatic reclosing onto permanent faults and fault distance calculation. Arc voltage amplitude and fault distance are calculated from the fundamental and third harmonics of the terminal voltages and currents phasors. The electric arc is modeled with its voltage wave shape defined numerically on the basis of a number of arc voltage records obtained in the high voltage laboratory. From the calculated arc voltage amplitude it can be concluded if the fault is transient arcing fault or permanent arcless fault. If the fault is permanent automatic reclosure should be blocked. The algorithm can be applied for adaptive autoreclosure, distance protection, and fault location. The results of algorithm testing through computer simulation are given.
机译:本文提出了一种新的数值谱域算法,用于阻止不成功的重合闸永久故障和故障距离的计算。电弧电压幅度和故障距离是根据端子电压和电流相量的基波和三次谐波计算得出的。根据在高压实验室获得的大量电弧电压记录,以数字化定义其电压波形的电弧模型。根据计算出的电弧电压幅度,可以得出故障是瞬时电弧故障还是永久性无电弧故障的结论。如果故障是永久性的,则应关闭自动重合闸。该算法可用于自适应自动重合闸,距离保护和故障定位。给出了通过计算机仿真进行算法测试的结果。