Operation of ground sensor relays under conditions of partial CT saturation

机译:CT部分饱和时地面传感器继电器的操作

获取原文

摘要

Since the publication of the paper by C.W. Barnett, et. al. (see IEEE Trans. Power Deliv., vol.8, no.3, p.884-97, 1993), concerning low-ratio current transformer (CT) saturation at high fault current and resulting mis-operation or nonoperation of overcurrent relays, there has been a great deal of well-directed concern about the problem reported in that paper. However, some of that concern has also been directed at the application of ground sensor relays to low-ratio CTs in resistance grounded industrial power systems, where no operational difficulties have been reported. The authors conducted a series of tests to determine if there is any cause for concern. These tests documented both the CT secondary current wave shapes and the relay contact closure times for several CT-relay-fault current combinations. This paper reports the results of these tests and presents conclusions concerning the adequacy of present practice in this field.
机译:自从C.W. Barnett等人发表论文以来。 al。 (请参阅IEEE Trans。Power Deliv。,第8卷,第3期,第884-97页,1993年),涉及高故障电流下的低比率电流互感器(CT)饱和以及过流继电器的误操作或不工作,该论文中报告的问题引起了很多直接的关注​​。但是,其中一些关注点还涉及将接地传感器继电器应用于电阻接地的工业电力系统中的低比率CT,在该领域中,尚无运行困难的报道。作者进行了一系列测试,以确定是否有任何令人担忧的原因。这些测试记录了几种CT继电器故障电流组合的CT次级电流波形和继电器触点闭合时间。本文报告了这些测试的结果,并提出了有关该领域当前实践的适当性的结论。