首页> 外文会议>Industry Applications Conference, 1995. Thirtieth IAS Annual Meeting, IAS '95., Conference Record of the 1995 IEEE >Design considerations for six pulse and twelve pulse diode rectifier systems operating under voltage unbalance and pre-existing voltage distortion with some corrective measures
【24h】

Design considerations for six pulse and twelve pulse diode rectifier systems operating under voltage unbalance and pre-existing voltage distortion with some corrective measures

机译:六脉冲和十二脉冲二极管整流器系统在电压不平衡和预先存在的电压畸变下工作的设计注意事项,并采取一些纠正措施

获取原文

摘要

In this paper design considerations for six pulse and twelve pulse diode rectifier systems operating under utility voltage unbalance and pre-existing harmonic voltage distortion is discussed. For a six pulse diode rectifier system it is shown that voltage unbalance and pre-existing voltage distortion in the utility generates uncharacteristic harmonics in the line currents. The amplitude of these uncharacteristic harmonics are shown to be amplified if the diode rectifier is operating in discontinuous conduction mode. For a twelve pulse diode rectifier system connected in parallel to feed a common DC link via interphase reactor it is shown that a small amount of impedance mismatch, utility voltage unbalance or pre-existing voltage distortion drastically affects the current sharing capability of the rectifier bridges. This in turn generates additional uncharacteristic and characteristic harmonics thereby increasing the THD. In order to mitigate these effects and ensure proper operation of diode rectifiers, specially designed line reactors termed as harmonic blocking reactors (HBRs) are introduced The analysis and design procedure for the HBRs are discussed. Simulation results illustrate improved performance. Experimental results from a laboratory prototype system show close agreement with theory.
机译:在本文中,讨论了在市电电压不平衡和预先存在的谐波电压失真下工作的六个脉冲和十二个脉冲二极管整流器系统的设计注意事项。对于六脉冲二极管整流器系统,显示出公用事业中的电压不平衡和预先存在的电压失真会在线路电流中产生不典型的谐波。如果二极管整流器在不连续导通模式下工作,这些非特征谐波的幅度将被放大。对于并联连接的十二个脉冲二极管整流器系统以通过相间电抗器馈入公共直流母线,显示出少量的阻抗失配,市电电压不平衡或预先存在的电压失真会严重影响整流桥的均流能力。这进而产生附加的非特征和特征谐波,从而提高了总谐波失真。为了减轻这些影响并确保二极管整流器正常工作,介绍了专门设计的被称为谐波阻断电抗器(HBR)的线路电抗器。对HBR的分析和设计过程进行了讨论。仿真结果说明了改进的性能。实验室原型系统的实验结果与理论非常吻合。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号