首页> 外文会议>Industrial and Commercial Power Systems Technical Conference, 1993. Conference Record, Papers Presented at the 1993 Annual Meeting >Predicting behavior of induction motors during electrical service faults and momentary voltage interruptions
【24h】

Predicting behavior of induction motors during electrical service faults and momentary voltage interruptions

机译:在电力故障和瞬时电压中断期间预测感应电动机的行为

获取原文

摘要

Dynamic simulations are used to predict the low voltage ride-through performance of three common motor and power source configurations. The objectives are to identify motor control and protection strategies that increase the motor's immunity to expected low voltage events while pointing out specific problems and opportunities. Configurations include transfer of a group of motors from one power source to another, ride-through of a single motor during low voltage events, and ride-through of a motor buffered by an adjustable-speed drive. Low voltage conditions match those expected to occur due to faults in the utility power system with the transformer connection considered.
机译:动态仿真用于预测三种常见电机和电源配置的低压穿越性能。目的是确定电动机控制和保护策略,以增加电动机对预期的低压事件的抵抗力,同时指出特定的问题和机会。配置包括将一组电动机从一个电源转移到另一个电源,在发生低压事件时使单个电动机穿越,以及由可调速驱动器缓冲的电动机穿越。低压条件与考虑到变压器连接的市电系统故障引起的预期条件相匹配。