首页> 外文会议>Electrical Insulation and Dielectric Phenomena, 1993. Annual Report., Conference on >Gas integrity and adsorbent performance in an SF/sub 6/ circuit breaker after test duty
【24h】

Gas integrity and adsorbent performance in an SF/sub 6/ circuit breaker after test duty

机译:测试工作后SF / sub 6 /断路器中的气体完整性和吸附剂性能

获取原文

摘要

A quality assessment of the SF/sub 6/ insulating gas in a circuit breaker following test duty was performed. In addition, exploratory research was undertaken to characterize the performance of adsorbent materials in relation to by-product dynamics. Gas samples were analyzed and revealed decomposition up to 16%. The usual by-products were identified; SOF/sub 2/ and SO/sub 2/ had the highest concentrations. Thermal desorption of the contaminated molecular sieve was successfully achieved. The thermally desorbed gaseous products correlated with the usual SF/sub 6/ by-products which resulted from arcing.
机译:在执行测试任务后,对断路器中的SF / sub 6 /绝缘气体进行了质量评估。此外,还进行了探索性研究,以表征与副产物动力学相关的吸附剂材料的性能。分析了气体样品后发现分解率高达16%。确定了常见的副产物; SOF / sub 2 /和SO / sub 2 /的浓度最高。成功地完成了受污染分子筛的热脱附。热解吸的气态产物与电弧产生的通常的SF / sub 6 /副产物相关。