Time domain analysis of distribution system harmonics. II. Interaction between harmonic sources and power system component

机译:配电系统谐波的时域分析。二。谐波源与电力系统组件之间的相互作用

获取原文

摘要

For pt.I see ibid., p.1241-6 (1992). The interaction between harmonic sources, other loads and the power system is investigated, using a power electronic simulator which performs an accurate time-domain analysis as described and verified in part I. An investigation is made of various load compositions involving power converter, three-phase induction motor, and constant impedance loads. The power system conditions studied include strong, weak, and parallel resonance. These results are compared with those from a simple Thevenin model of the power system to establish the limit of the model's validity. An expression showing how the harmonic current injected into the power system is affected by load comparison is derived.
机译:关于pt,我参见同上,第1241-6页(1992年)。使用电力电子模拟器对谐波源,其他负载与电力系统之间的相互作用进行了研究,该电力模拟器执行了如第一部分所述并进行了准确的时域分析。相位感应电动机和恒定阻抗负载。研究的电力系统条件包括强,弱和并联谐振。将这些结果与电力系统简单的戴维南模型的结果进行比较,以确定模型有效性的极限。得出一个表达式,该表达式显示了负载比较如何影响注入电力系统的谐波电流。