Continuous-process plants, such as petro-chemical industries and paper mills with thermomechanical pulping, are being designed with fewer and larger components arranged in single-train configurations. Maintaining operating continuity with fewer components requires high equipment reliability. Motor controls for large components are using magnetic contactors equipped with automatic undervoltage reclosing. A voltage dip where contractors drop open and reclose can be very serious because of the nature of the motors and their driven loads during voltage transients. The general nature of the problem and criteria for safe reclosing or transfer of several motors on the same bus are presented. The mathematical development and modeling techniques for induction and synchronous motors are indicated, and simple easy-to-use expressions are given for determining the currents and torques due to out-of-phase reclosing. Various protective schemes against out-of-phase reclosing and transfer, as well as methods of riding through voltage dips, are discussed.
机译:正在设计连续过程的工厂,例如石油化学工业和具有热机械制浆的造纸厂,其设计是将越来越少的组件布置成单列配置。用更少的组件来保持操作的连续性需要很高的设备可靠性。大型组件的电机控制使用带有自动欠压重合闸功能的电磁接触器。由于电压瞬变期间电机及其驱动负载的特性,承包商突然断开和重新闭合的电压跌落可能会非常严重。介绍了问题的一般性质以及在同一总线上安全重合闸或转移多个电动机的标准。给出了感应电动机和同步电动机的数学开发和建模技术,并给出了简单易用的表达式来确定由于异相重合闸而引起的电流和转矩。讨论了防止异相重合闸和转移的各种保护方案,以及克服电压突降的方法。

著录项

相似文献

  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号