首页> 外文会议>Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society >Predicting and testing the effectiveness of voltage-correcting capacitors on two 12 kV distribution lines
【24h】

Predicting and testing the effectiveness of voltage-correcting capacitors on two 12 kV distribution lines

机译:预测和测试两条12 kV配电线路上的电压校正电容器的有效性

获取原文

摘要

Techniques for calculating the quantity and locations of voltage-correcting capacitors on distribution lines have been described in many studies. Two different computer models to optimize the sizes and placement of capacitors on two 12 kV lines were used. One line is 16 km (10 miles) long with the biggest load, up to 2000 kVA, at its end. The other is 10.5 km (6.5 miles) long. After the capacitors were installed, loads and voltages were measured along each line while supplementing existing loads with load banks, one rated 2944 kVA and the other 500 kW. 200 HP fire pumps were started to collect transient performance. The measured currents and power factors were entered into the computer models to calculate voltages along the lines. Predicted voltages were, on the average, within 0.85% of measured values.
机译:在许多研究中已经描述了用于计算配电线上的电压校正电容器的数量和位置的技术。使用了两种不同的计算机模型来优化两条12 kV线路上电容器的尺寸和位置。一条线长16公里(10英里),最大负载在末端,最大负载为2000 kVA。另一个长10.5公里(6.5英里)。安装电容器后,在测量每条线路的负载和电压的同时,用负载组(一个额定值为2944 kVA的负载组和另一个500 kW的负载组)补充了现有负载。开始使用200马力的消防泵来收集瞬时性能。将测得的电流和功率因数输入计算机模型,以计算沿线的电压。预测电压平均在测量值的0.85%以内。