首页> 外文会议>Electrical Insulation, 1990., Conference Record of the 1990 IEEE International Symposium on >Improvement in the measurements of partial discharges in hydrogenerators through high-frequency grounding of couplers
【24h】

Improvement in the measurements of partial discharges in hydrogenerators through high-frequency grounding of couplers

机译:通过耦合器的高频接地改善水轮发电机局部放电的测量

获取原文

摘要

In the balanced coupler technique for the detection of discharges in rotating machines, it is common practice to omit grounding the coaxial-line shielding near the couplers in order to avoid induced current loops. Recent measurements demonstrate that providing a high-frequency ground to the coaxial shielding at the capacitive couplers reduces the magnitude of the high-frequency signal propagating along the outside shield. The signal coupling between adjacent coaxial cables is thus reduced, providing a higher signal level and a better signal-to-noise ratio at the detector end.
机译:在用于检测旋转电机中的放电的平衡耦合器技术中,通常的做法是在耦合器附近省略同轴线屏蔽的接地,以避免产生感应电流环路。最近的测量表明,在电容耦合器上为同轴屏蔽层提供高频接地会降低沿外部屏蔽层传播的高频信号的幅度。因此,减少了相邻同轴电缆之间的信号耦合,从而在检测器端提供了更高的信号电平和更好的信噪比。