【24h】

New very low frequency methods for testing extruded cables

机译:用于测试挤压电缆的全新超低频方法

获取原文

摘要

A novel digital instrument has been developed for loss-factor measurement. It is program controlled, easy to operate, and has a measurement resolution of tan delta -0.1 Hz=0.01%. The loss angle is determined by a range measurement of crossovers of current and voltage. At 0.1 Hz tan delta has a considerably larger dynamic than at 50 Hz; for this reason tan delta -0.1 Hz is especially suitable for diagnostics of the operational efficiency of plastic cables. Measurements on naturally aged cables showed that there is a definite correlation between increased tan delta -0.1 Hz and reduced breakdown voltage. The tan delta -0.1 Hz measurement carried out at a nominal voltage U/sub 0/ allows nondestructive evaluation if the cable has been damaged by long water trees. With a 0.1-Hz test at 3U/sub 0/ for approximately 1 h, serious weak points can be detected in the plastic insulation.
机译:已经开发了用于损耗因子测量的新型数字仪器。它是程序控制的,易于操作,并且测量分辨率为tan delta -0.1 Hz = 0.01%。损耗角通过对电流和电压的跨接范围进行测量来确定。 tanδ在0.1 Hz时的动态比在50 Hz时大得多。因此,tan delta -0.1 Hz特别适用于诊断塑料电缆的工作效率。在自然老化的电缆上进行的测量表明,tanδ-0.1 Hz的增加与击穿电压的减少之间存在明确的相关性。如果电缆已被长水树损坏,则在标称电压U / sub 0 /下执行的tan del -0.1 Hz测量可以进行无损评估。通过在3U / sub 0 /处进行0.1Hz的测试大约1小时,可以在塑料绝缘中检测到严重的薄弱点。