Effect of DC tests on induced space charge

机译:直流测试对感应空间电荷的影响

获取原文

摘要

Poling-induced space charges in peeled samples of AC-aged, DC-tested cables were studied using the thermal pulse technique. Samples were poled at approximately 0.12 MV/cm for 3.5 h at 70 degrees C using the same polarity as that used for the DC tests. Previous work seemed to indicate that DC testing could have permanent effects which could be detected by the amount of poling-induced charge. An attempt was made to examine this by using three samples with about the same length of AC aging but with different amounts of DC testing. The sample with one DC test and the sample with 23 DC tests were appreciably oxidized, whereas the sample with 11 DC tests was not oxidized. In addition, when the sample was pulsed from the face exposed to the positive poling electrode, a negative space charge was observed. When it was pulsed from the opposite face, a positive space charge was observed. The space charge decay was found to be asymmetric. AT 70 degrees C, the negative space charge decays faster than the positive space charge. At 60 degrees C, the decay was observed to be about the same on both sides. When the poling field is small, both sides have a positive space charge. For larger poling fields, the space charge in the film close to the positive electrode is negative.
机译:使用热脉冲技术研究了交流老化,经过直流测试的电缆的剥皮样品中由极化引起的空间电荷。样品在70摄氏度下以约0.12 MV / cm的速度极化3.5 h,极性与DC测试中使用的极性相同。先前的工作似乎表明,直流测试可能具有永久性影响,可以通过极化感应电荷的量来检测。试图通过使用三个具有相同的AC老化时间但具有不同的DC测试量的样品来对此进行检查。具有一个直流测试的样品和具有23个直流测试的样品被明显氧化,而具有11个直流测试的样品没有被氧化。另外,当样品从暴露于正电极的表面脉冲化时,观察到负空间电荷。当它从另一面发出脉冲时,观察到正的空间电荷。发现空间电荷衰减是不对称的。在70摄氏度时,负空间电荷的衰减快于正空间电荷的衰减。在60摄氏度时,观察到两侧的衰减大致相同。当极化场较小时,双方都具有正的空间电荷。对于较大的极化场,靠近正极的薄膜中的空间电荷为负。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号