Results of full-scale fire tests with electrical nonmetallic conduit and insulated wire in a vertical riser duct

机译:在垂直立管中使用非金属电气导管和绝缘电线进行全面火灾测试的结果

获取原文

摘要

Full-scale fire tests were conducted during the summer of 1987 at the New York State Academy of Fire Science in Montour Falls, New York to determine if the results of small-scale smoke and toxicity tests reflected real-world conditions represented by full-scale testing. These tests were performed with 20ft-long sample bundles of conduit and wire hanging vertically in a 10 in-square riser duct installed in the Academy's three-story, reburnable, arson simulation and fire-training building. Present commercially available materials and novel reduced-emission materials were tested, and the results compared. The full-scale test results correlated with those from small-scale tests, with the reduced-emissions material producing substantially less smoke and being nonlethal under the test conditions.
机译:1987年夏季,在纽约州蒙图福尔斯的纽约州消防科学研究院进行了全面的火灾测试,以确定小型烟雾和毒性测试的结果是否反映了以实际规模为代表的现实条件测试。这些测试是通过将20英尺长的导线管和电线样本束垂直悬挂在10平方英寸的竖管中进行的,该竖管安装在学院的三层,可再燃,纵火模拟和消防训练大楼中。测试了目前市售的材料和新型减排材料,并对结果进行了比较。满量程测试结果与小规模测试的结果相关,排放量降低的材料产生的烟雾少得多,并且在测试条件下不具有致命性。