Taking LiBr-H2O liquid desiccant system with the form of counter-flow, random packed and internal solution cycle as the object. Numerical study was carried out on the effect of circulation flow ratio to the performance of dehumidifier (regenerator), as well as to the dehumidification capacity and the required cooling load of dehumidification. The numerical simulation results show that while the circulation flow ratio became larger, the inlet solution’s temperature of dehumidifier (regenerator) got higher (lower), cooling load of cooler became smaller, meantime the dehumidification capacity and the required cooling load of dehumidification also became smaller. By controlling the circulation flow ratio, the performance of dehumidification (regeneration) and cooling load can be regulated.
机译:以逆流,无规填充和内部溶液循环形式的LiBr-H2O液体干燥剂系统为对象。进行了循环流量比对除湿器(蓄热器)性能,除湿能力和除湿所需冷却负荷的影响的数值研究。数值模拟结果表明,当循环流量增大时,除湿器(蓄热室)的入口溶液温度升高(降低),冷却器的冷却负荷减小,同时除湿能力和所需的除湿冷却负荷也变小。 。通过控制循环流量比,可以调节除湿(再生)性能和冷却负荷。