THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS

机译:热带地区文化殿堂的热舒适

获取原文

摘要

A field study was conducted in six lecture halls DK1-DK6 of the Faculty of Engineering at University of Malaya, Kuala Lumpur to assess the thermal conditions during the lecture session. Comfort parameters were measured to analyze the acceptability of the thermal comfort simultaneously when 178 students answered a survey questionnaire on their thermal perception/sensation of the indoor climate. The measured data includes air temperature, mean radiant temperature, relative humidity, air velocity and personal variables. The response of the occupants in the lecture hall DK6 only is fulfilling the ASHRAE Standard 55, because PPD in this lecture hall is 5.8, whereas that in other lecture halls is above 10. Besides, AMV and PMV have been compared. Fanger’s model was used to calculate the neutral operative temperature (24.6°C), whereas the questionnaire data used in the TSV analysis gives higher value (25.3°C) for the neutral operative temperature. This is in good agreement with the neutral operative temperature (25.4°C) for Hong Kong. The humidity in the lecture halls DK1, DK4 and DK5 was below and that of the lecture halls DK2, DK3 and D6 was above the recommended range 50-60% RH. The air velocity in all the six lecture halls was below 0.2 m/s for normal room air distribution. The air velocity in the lecture hall DK6 was 0.08 m/s, which is too low. Metabolism in each hall was ≤ 1.2 met for light and primarily sedentary activity. The clo value in each lecture hall was above 0.55 clo for average people. Findings of this field study are useful in designing HVAC systems with energy savings for university lecture halls in the tropics.
机译:在吉隆坡马来亚大学工程学院的六个演讲厅DK1-DK6中进行了现场研究,以评估演讲期间的热条件。当178名学生回答了关于他们对室内气候的热感知/感知的调查问卷时,同时测量了舒适性参数以分析热舒适性的可接受性。测得的数据包括空气温度,平均辐射温度,相对湿度,空气速度和个人变量。演讲厅DK6中的人员响应仅满足ASHRAE标准55,因为该演讲厅中的PPD为5.8,而其他演讲厅中的PPD为10以上。此外,还对AMV和PMV进行了比较。 Fanger模型用于计算中性操作温度(24.6°C),而TSV分析中使用的调查表数据给出了中性操作温度的较高值(25.3°C)。这与香港的中性工作温度(25.4°C)非常吻合。演讲厅DK1,DK4和DK5的湿度低于湿度,而演讲厅DK2,DK3和D6的湿度高于建议的湿度50-60%RH。对于正常的室内空气分配,六个演讲厅中的所有风速均低于0.2 m / s。演讲厅DK6中的风速为0.08 m / s,太低。每个大厅的新陈代谢量≤1.2,主要是久坐活动。每个演讲厅的clo值对于普通人来说都高于0.55 clo。这项现场研究的结果对于为热带大学的演讲厅设计节能的HVAC系统很有用。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号