In this paper, protection coordination problem of directional overcurrent relays (DOCRs) is discussed by simultaneously selecting time-current characteristic curve and optimizing settings of the relays. For this, DOCRs are assumed to be associated with three setting variables which are time multiplier-setting (TMS), plug-setting (PS) and curve-setting (CS) to obtain their correct operating times. The TMS and PS of all the relays are considered as continuous variables which are possible with numerical/digital relays whereas the CS is considered as a discrete variable and are associated with the selection of the time-current characteristics of the relay among normal inverse, very inverse and extremely inverse. The proposed coordination studies have been investigated on the IEEE 14-bus test system.
机译:本文通过同时选择时间-电流特性曲线并优化继电器的设置,讨论了定向过电流继电器(DOCR)的保护协调问题。为此,假定DOCR与三个设置变量相关联,它们是时间乘数设置(TMS),插塞设置(PS)和曲线设置(CS),以获得正确的工作时间。所有继电器的TMS和PS都被认为是连续变量,数字/数字继电器可以做到这一点,而CS则被认为是离散变量,并且与继电器的时电流特性的选择相关,通常为反时限,逆和极逆。建议的协调研究已在IEEE 14总线测试系统上进行了研究。