首页> 外文会议>Asia Conference on Power and Electrical Engineering >Case Analysis of 220 kV Oil-immersed Current Transformer Defect
【24h】

Case Analysis of 220 kV Oil-immersed Current Transformer Defect

机译:220 kV油浸式电流互感器故障的案例分析

获取原文

摘要

This paper introduces the case of abnormal live detection data of 220 kV Oil-Immersed Current T ransformer in a 220 kV substation during live detection. When the live detectors find the abnormal equipment, they synthetically analyze the current with other detection methods such as infrared thermal imaging temperature measurement technology and relative dielectric loss live detection technology. At the same time, the equipment is disintegrated, and the capacitance screen is peeled off layer by layer. Finally, waxy hydrocarbon polymer is found in the capacitance screen of the inner bottom of the current transformer. Combined with the live test data and the disintegration results of the equipment, the inspectors check the same type of equipment one by one, and put forward the treatment methods and suggestions for rectification.
机译:本文介绍了在220 kV变电站带电检测过程中出现异常的220 kV油浸电流互感器带电检测数据的情况。当带电检测器发现异常设备时,他们会使用其他检测方法(例如红外热成像温度测量技术和相对介电损耗带电检测技术)对电流进行综合分析。同时,设备被分解,并且电容屏被一层一层地剥离。最后,在电流互感器内底的电容屏中发现了蜡状烃聚合物。检验人员结合现场测试数据和设备的分解结果,对同类型的设备进行了逐一检查,并提出了处理方法和整改建议。