摘要

The fault analysis of AC outlets in VSC HVDC power grid is the basis of AC protection configuration. This paper analyzes the influence of negative sequence suppression strategy on negative sequence current and positive and negative sequence voltage of converter station, studies the influence of outer loop limiting controller on short-circuit current, analyzes the mechanism of low-voltage limiting strategy on positive sequence current, and obtained the impedance angle of AC outlets fault in VSC HVDC power grid, The simulation results show that the control strategy has an effect on the amplitude and phase angle of the short-circuit current. This study provides a basis for the analysis of the influence of the VSC HVDC power grid on the AC protection.
机译:VSC HVDC电网中交流电源插座的故障分析是交流保护配置的基础。本文分析了负序抑制策略对换流站负序电流和正负序电压的影响,研究了外环限幅控制器对短路电流的影响,分析了低压限幅策略对正序的影响机理。仿真结果表明,控制策略对短路电流的幅值和相角有影响。该研究为分析VSC HVDC电网对交流保护的影响提供了基础。