This paper analyses N-1 security in an interconnected ac/dc transmission system using power transfer distribution factors (PTDFs). In the case of a dc converter outage the power needs to be redistributed among the remaining converter to maintain power balance and operation of the dc grid. The redistribution of power has a sudden effect on the power-flow in the interconnected ac system. This may cause overloading of lines and transformers resulting in disconnection of equipment, and as a consequence cascading failure. The PTDF is used as a method to analyze and avoid violating limits by in the dc voltage control design consider the power distribution for a converter outage. By proper design and utilizing the proposed method increases the N-1 security and the secure transfer limits. This article proposes a method which minimizes the 2-norm of the sum of the PTDFs with constraints of not violating any line or transformer limits. Simulations were performed in a model of the Nordic power system where a dc grid is placed on top. The simulation supports the method as a tool to consider transfer limits in the grid to avoid violate the same and increase the security after a converter outage.
机译:本文使用电力传输分布因子(PTDFS)分析了互连的AC / DC传输系统中的N-1安全性。在DC转换器中断的情况下,需要在剩余的转换器中重新分配电源,以保持功率平衡和DC网格的操作。功率的重新分配对互连的AC系统中的电流突然影响。这可能导致线路和变压器的过载导致设备断开,并且作为级联故障。 PTDF用作分析和避免在直流电压控制设计中违反限制的方法,考虑转换器中断的功率分布。通过适当的设计和利用所提出的方法,增加了N-1安全性和安全转移限制。本文提出了一种方法,该方法最小化了PTDF的2规范,而没有违反任何线或变压器限制的限制。在北欧电力系统的模型中执行模拟,其中DC网格放置在顶部。模拟支持该方法作为一种工具,以考虑网格中的传输限制以避免违反相同并提高转换器中断后的安全性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号