Safe Grounding Grid Design for HVDC Converter Station

机译:高压直流换流站的安全接地网设计

获取原文

摘要

The main goal of this paper is presenting an optimum and safe design for the proposed high voltage direct current (HVDC) grounding grid for converter station at Badr city in Egypt for uniform and non-uniform soil resistivities. Also, the paper discusses the difference between HVDC grounding grids and high voltage alternating current (HVAC) ones. CYMGRD software was used to estimate the step and touch potentials at the soil surfaces at different conditions. The consequences show that the computed results for step and touch potentials are below the safe limits for human in cases of continuous normal and fault conditions for uniform and non-uniform soil resistivities. From results, touch voltage in a non-uniform layer in continues operation is 17.65 V, and equal to 57. 37V in fault operation.
机译:本文的主要目的是为埃及Badr市换流站建议的高压直流(HVDC)接地网提供最佳和安全的设计,以实现均匀和不均匀的土壤电阻率。此外,本文还讨论了HVDC接地网与高压交流(HVAC)接地网之间的区别。 CYMGRD软件用于估算不同条件下土壤表面的阶跃和接触电位。结果表明,在连续的正常和断层条件下,对于均匀和不均匀的土壤电阻率,步进和接触电势的计算结果低于人类的安全极限。从结果可以看出,在连续操作中,非均匀层中的触摸电压为17.65 V,在故障操作中等于57. 37V。