首页> 外文会议>International Symposium INFOTEH-JAHORINA >Testing the algorithm fordetection of arcing faults on overhead lines
【24h】

Testing the algorithm fordetection of arcing faults on overhead lines

机译:检测架空线上的电弧故障算法

获取原文

摘要

Large majority of system faults are transient nature and they can be effectively eliminated with automatic reclosing of power lines. However, switcher devices are unnecessary stressed with autoreclosers in case of permanently faults, because fault will not be cleared with switching off the transmision lines. This paper analyzes the algorithm for estimating the location of the fault and the arc voltage, and gives the possibility to separate permanently faults from the transient faults. Information of the type of fault (permanently or transient) gives the possibility to block autoreclosers when the fault is not transient. Algorithm is applied on the threephase model of the transmission line formed by MATLAB/Simulink.
机译:大多数系统故障是瞬态性质,可以通过自动重新连接电力线来有效地消除它们。但是,在永久故障的情况下,在自动弹性器中不需要切换器设备,因为断开切断线不会清除故障。本文分析了估算故障位置和电弧电压的算法,并提供了从瞬态断层中分离永久性故障的可能性。故障类型(永久性或瞬态)的信息可以在故障不瞬态时阻止自动弹性器。 Matlab / Simulink形成的传输线的三相模型应用算法。