A single pole to ground fault location method for HVDC transmission lines based on coupling characteristics

机译:基于耦合特性的高压直流输电线路单极接地故障定位方法

获取原文

摘要

In this paper, coupling coefficient between conductors is demonstrated as a superior indicator for single pole fault location. A method is proposed to locate faults via estimating the coupling coefficient with the help of single end current measurements taken within the first mille-second after the fault created wave reach the terminal. As the coupling coefficient is not dependent on fault resistance, the single pole fault location can be done with the help of pre-calculated inverse coupling coefficients estimated for some metallic faults applied at regular intervals. The performances of the proposed single end fault location scheme are evaluated in long bipole line commutated converter based HVdc transmission system as well as in a medium length monopole HVdc transmission configuration. Higher accuracy is observed despite of simplicity of the proposed scheme.
机译:在本文中,导体之间的耦合系数被证明是单极故障定位的优良指标。提出了一种在故障产生波到达终端后的第一毫秒内通过单端电流测量来估计耦合系数来定位故障的方法。由于耦合系数不依赖于故障电阻,因此可以通过对以规则间隔应用的某些金属故障进行估算的逆耦合系数来完成单极故障定位。在基于长双极换向变换器的HVdc传输系统以及中等长度的单极HVdc传输配置中,对所提出的单端故障定位方案的性能进行了评估。尽管提出的方案简单,但观察到较高的精度。