首页> 外文会议>IET International Conference on AC and DC Power Transmission >Overvoltage analysis of flexible HVDC converter station
【24h】

Overvoltage analysis of flexible HVDC converter station

机译:柔性直流换流站过电压分析

获取原文

摘要

In order to solve the impact of photovoltaic volatility on power systems, flexible HVDC transmission technology is more and more used for photovoltaic grid connection. As the most important component of flexible HVDC transmission systems, the characteristics of the equipment in the flexible HVDC converter station are of great significance to the safe and stable operation of the HVDC transmission system. When the AC/DC side of the converter station fails or is struck by lightning, the converter station equipment will have an overvoltage. In severe cases, it will damage the equipment in the converter station and threaten the safe and stable operation of the system. Therefore, this paper comprehensively considers the various overvoltage conditions of a ±30kV converter station with modular multilevel converter (MMC), and uses PSCAD/EMTDC for simulation calculation. According to the calculation results, the arrester configuration of the converter station is analysed, and the results can be used for equipment selection and engineering design.
机译:为了解决光伏波动对电力系统的影响,柔性直流输电技术越来越多地用于光伏并网。柔性直流换流站作为柔性直流输电系统中最重要的组成部分,其设备特性对柔性直流输电系统的安全稳定运行具有重要意义。当换流站的AC/DC侧发生故障或被雷击时,换流站设备将产生过电压。严重时会损坏换流站设备,威胁系统的安全稳定运行。因此,本文综合考虑了采用模块化多电平变流器(MMC)的±30kV换流站的各种过电压情况,并采用PSCAD/EMTDC进行了仿真计算。根据计算结果,对换流站的避雷器配置进行了分析,其结果可用于设备选型和工程设计。