首页> 外文会议>International Conference on Electrical and Electronics Engineering >Thermal Analyses for a Simplified Medium-Voltage Switchgear: Numerical and Experimental Benchmark Studies
【24h】

Thermal Analyses for a Simplified Medium-Voltage Switchgear: Numerical and Experimental Benchmark Studies

机译:简化的中压开关柜的热分析:数值和实验基准研究

获取原文

摘要

Present study reports experimental and computational results obtained for a switchgear, where its critical components such as busbars, and tulip contacts are numerically modeled. In the experiment, thermocouples are used to measure the temperature at several locations of the switchgear at operating condition. One-way coupled EMAG and CFD computations are performed to obtain eddy current losses first, then the temperature and velocity distributions are obtained for the natural convection in and out of the model that is induced by the losses. Comparison of the obtained temperature distributions show that the experimental and computational results are in similar trend in general. In order to understand the causes of local discrepancies in the results, it is considered to conduct computations on a high performance computing environment for a more realistically modelled electrical components.
机译:本研究报告了开关柜的实验和计算结果,其中对开关柜的关键组件(如母线和郁金香形接点)进行了数值建模。在实验中,热电偶用于在操作条件下测量开关柜几个位置的温度。首先进行单向耦合的EMAG和CFD计算,以获得涡流损耗,然后针对由损耗引起的模型的自然对流和自然对流,获得温度和速度分布。对所获得的温度分布的比较表明,实验和计算结果总体上具有相似的趋势。为了了解结果中局部差异的原因,可以考虑在高性能计算环境中进行更逼真的建模的电气组件的计算。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号