首页> 外文会议>International Conference on Electrical and Electronics Engineering >The Effects of Overvoltage Aging on 20 kV XLPE Power Cable
【24h】

The Effects of Overvoltage Aging on 20 kV XLPE Power Cable

机译:过电压老化对20 kV XLPE电力电缆的影响

获取原文

摘要

XLPE power cables have been widely used with the development of city power grid because of their obvious advantages. To improve the reliability of power supplies and meet the requirements of urban landscaping, however, faults in the electricity distribution grid and load/demand imbalance cause degradation in underground cables. This degradation leads the cable to be aged and reduce its lifetime. Therefore, it is important to examine the behavior of the XLPE insulated cable dielectric parameters. In this study, a 12/20 kV XLPE cable was aged using 60 kV overvoltage and this voltage was applied to the test samples for 15 minutes intervals. 80 cycles of aging were carried out and dissipation factor (tanô), dielectric losses (Pk) and partial discharge (PD) measurements were performed after each aging cycle. OMICRON CPC100/CPTD1 was used to measure dissipation factor (tanô), dielectric losses (Pk) and OMICRON MPD600 was used to measure partial discharge.
机译:XLPE电力电缆具有明显的优势,已广泛应用于城市电网的发展。但是,为了提高电源的可靠性并满足城市环境美化的要求,配电网的故障和负载/需求不平衡会导致地下电缆的性能下降。这种退化会导致电缆老化,并缩短其使用寿命。因此,重要的是检查XLPE绝缘电缆介电参数的性能。在这项研究中,使用60 kV过电压对12/20 kV XLPE电缆进行了老化,并以15分钟的间隔将该电压施加到测试样品上。进行了80个老化周期,并在每个老化周期后进行了损耗因数(tanô),介电损耗(Pk)和局部放电(PD)测量。 OMICRON CPC100 / CPTD1用于测量损耗因子(tanô),介电损耗(Pk),而OMICRON MPD600用于测量局部放电。