首页> 外文会议>International Conference on Power and Energy Systems >Core Loss Studies using FEM of a Three Phase Isolation Transformer under Harmonic Conditions
【24h】

Core Loss Studies using FEM of a Three Phase Isolation Transformer under Harmonic Conditions

机译:谐波条件下使用三相隔离变压器的有限元法进行铁损研究

获取原文

摘要

This paper aims to investigate the effect of voltage harmonics on transformer core losses. A three-dimensional finite element method (FEM) is employed to model a three-phase isolation transformer supplied by a contaminated power source. The effect of harmonics is accurately modelled in FEM. The proposed model in FEM is verified by experiment where the results obtained using FEM show good agreement with experimental results. Different case studies with different harmonic conditions are investigated. The results show an increase in the core loss value up to 67.3% when the input voltage is formed based on the highest percentage of harmonic orders stated in the IEC 61000-3-6. As the core loss is always present, the energy loss continuously accumulates. Thus, voltage harmonics contribute to increase in the core loss in transformers.
机译:本文旨在研究电压谐波对变压器铁芯损耗的影响。使用三维有限元方法(FEM)对由污染电源提供的三相隔离变压器进行建模。谐波的影响已在FEM中精确建模。通过实验验证了所提出的有限元模型,其中使用有限元方法获得的结果与实验结果吻合良好。研究了在不同谐波条件下的不同案例研究。结果表明,根据IEC 61000-3-6中规定的最高谐波阶次形成输入电压时,铁芯损耗值最多可增加67.3%。由于铁心损耗始终存在,因此能量损耗会不断累积。因此,电压谐波会导致变压器铁芯损耗的增加。