首页> 外文会议>International Conference on Power and Energy Systems >Modifying IEC 60909 Standard to Consider Fault Contribution from Renewable Energy Resources Utilizing Fully-Rated Converters
【24h】

Modifying IEC 60909 Standard to Consider Fault Contribution from Renewable Energy Resources Utilizing Fully-Rated Converters

机译:修改IEC 60909标准以考虑使用全额定转换器的可再生能源造成的故障

获取原文

摘要

This paper studies the performance of the latest version of the IEC 60909 standard for steady-state fault calculations in power systems including high penetration of renewable energy resources (RESs) utilizing fully-rated converters. The study proposes a simple method to enhance the accuracy of the IEC 60909 in assessment of steady-state fault levels with high penetration of RESs utilizing fully-rated converters. Our improved IEC 60909 method includes the reactive current injection of such resources more precisely according to the grid code, hence results in a better performance of steady-state fault calculations. The simulation results have shown an enhanced accuracy of our methodology compared to the latest version of the IEC 60909. Our findings are confirmed using the IEEE 14-bus test system in DIgSILENT PowerFactory.
机译:本文研究了最新版本的IEC 60909标准的性能,该标准用于电力系统中的稳态故障计算,包括使用全额定转换器的可再生能源(RES)的高渗透率。该研究提出了一种简单的方法,该方法可以提高IEC 60909在使用全额定值转换器对RES进行高渗透率的稳态故障等级评估中的准确性。我们改进的IEC 60909方法包括根据电网规范更精确地注入此类资源的无功电流,因此可实现更好的稳态故障计算性能。仿真结果表明,与最新版本的IEC 60909相比,我们的方法具有更高的准确性。我们的发现得到了DIgSILENT PowerFactory中使用IEEE 14总线测试系统的证实。